Directional Way Finder Safety Light - AlightForLife®

A Directional Way Finding Fire Safety LED light that is capable of being actuated by sensing the sound of smoke sounders, or through a non-sounding smoke-head in communal parts of buildings with general needs, for example, stay put policy.

Technical Specification

Dimensions

360 mm x 112 mm x 53.5 mm

Construction

Injection molded fire retardant ABS C/W translucent directional indicator window.

Color is RAL**** (These units can be color coded based on request in order to match thedecor). IP Rating IP50.

Electrical

Power Supply voltage 90­-264 Vac 47­-63 Hz
ROHS Compliant.
Earth Leakage Class II no earth.

CE and EMC tested to the following.

EN61000-4­-8
EN61000-­4­-3
EN61000-­4­-6
EN61000-­6-1
EN61000-­6-2

Stand-by Power If Mains Fail

Battery - 12 V 2.1 Ah sealed lead acid.

Selectable timed disconnect in order to avoid deep discharge of the battery.

An on-board charging circuit is used for maintaining the battery charge.

Audible Detection Circuit

The audio detection circuit is used for monitoring the background audio levels and the unit will then activate the direction indication lamp when the sound is greater than the audio level setting. When it is sustained for more than 6 or 12 seconds (selectable), it will be possible to adjust the audio threshold in order to suit the environment.

Automatic Light level Detection (Option)

The unit can be set into a mode where audio will only be detected in lower light level, and this is selectable through the on-­board dip switch settings.

Lux Output

Exceeds 20 LUX output @ 1 meter distance. Measured in area registering 0 (zero) LUX before and exceeding 20 LUX after the light is activated and illuminated.

Self-Test Function

The unit will carry out a self test on the unit where it will operate the light for 1s and this will then be detected by an on-board sensor, if the test is detected the light will continue in the normal operation.

If the test is not detected, then a red fail LED will flash to highlight the occurrence of a failed test.

The test will be repeated two more times and if these also fail then the fault light will be illuminated in the steady state in order to show there has been a failure. This can only be reset by total power down of the unit. There is a fault buzzer on the unit, which can be selected by using switch 6.

On-board Switch Settings

Switch Number Switch Position Function
1 ON
OFF
Daylight Sensor Off
Daylight Sensor On
2 ON
OFF
Direction Arrow Flash Mode
Direction Arrow Steady Mode
3 ON
OFF
Audio Sense Time 12 Seconds
Audio Sense Time 6 Seconds
4 ON
OFF
Standby Cut Off Time 8 hrs
Standby Cut Off Time 4 hrs
5 ON
OFF
Light is in ON Position (maintained)
Normal mode — Off until triggered
6 ON
OFF
Fault Buzzer Enabled
Fault Buzzer Disabled

Note: When making any changes we recommend that the unit is down powered.

Battery Specification

SPECIFICATIONS
Nominal voltage 12 V
20 hr rate Capacity to 1.75 VPC at 20 °C 2.1 Ah
10 hr rate Capacity to 1.75 VPC at 20 °C 1.9 Ah
DIMENSIONS
Length 178 (±1) mm
Width 34 (±1) mm
Height   mm
(height over terminals) 64 (±2) mm
Mass (typical) 0.82 kg
TERMINAL TYPE
FASTON (Quickfit / release) 4.75 mm
OPERATING TEMPERATURE RANGE
Storage -20 °C to +60 °C
Charge -15 °C to +50 °C
Discharge -20 °C to +60 °C
STORAGE
Capacity loss per month at 20 °C (approx.) 3 %
CASE MATERIAL
Standard Option ABS (UL.94:HB)
Flame retardant option (FR) ABS (UL94:VO)
CHARGE VOLTAGE
Float charge voltage at 20 °C 13.65 (±1%)
2.275 (±1%)
V
V/cell
Float charge voltage temperature correction factor (for variations from the standard 20 °C) -3 mV/cell/°C
Cyclic (or boost) charge at 20 °C 14.5 (±3%)
2.42 (±3%)
V
V/cell
Cyclic charge voltage temperature correction factor (for variations from the standard 20 °C) -4 mV/cell/°C
CHARGE CURRENT
Float charge current limit No limit A
Cyclic (or boost) charge current limit 0.525 A
MAXIMUM DISCHARGE CURRENT
1 Second 63 A
1 minute 21 A
SHORT-CIRCUIT CURRENT & INTERNAL RESISTANCE
(according to EN IEC 60866-21)
Internal resistance N/A
Short-circuit current N/A A
IMPEDANCE
Measured at 1 kHz 90
PERFORMANCE & CHARACTERISTICS
Refer to the technical manual NP  
DESIGN LIFE
EUROBAT Classification: Standard Commercial 3 to 5 years
Yuasa design life @ 20 °C up to 5 years
SAFETY
Installation
Can be installed and operated in any orientation except permanently inverted.
Handles
Batteries must not be suspended by their handles (where fitted).
Vent valves
Each cell is fitted with a low pressure release valve to allow gasses to escape and then reseal.
Recycling
Batteries must be recycled at the end of life in accordance with local and national laws and regulations.

AlightForLife® Housing Specification

General Purpose ABS, POLYLAC® Characteristics

Properties ISO Test Condition Unit PA 757
MVI 1133 220 °C x 10 kg ml/10 min 22
Mass Density 1183 23 °C g/cm3 1.05
Tensile Strength 527 50 mm/min. yield
50 mm/min. break
MPa
MPa
54
37
Tensile Elongation 527 50 mm/min % 20
Flexural Strength 178 2 mm/min MPa 76
Flexural Modulus 178 2 mm/min GPa 2.2
Izod Impact Strength 180/1A Notched
Unnotched
KJ/m2
KJ/m2
18
60
Charpy Impact 179 Notched
Unnotched
KJ/m2
KJ/m2
20
NB
Vicat Softening Temp. 306 50 °C/hr; 1 kg
50 °C/hr; 5 kg
°C
°C
104
100
H.D.T /A 75 1.8 MPa, unanneal
1.8 MPa, anneal
°C
°C
88
98
Ball Indentation Hardness 2039-1 H358/30 - 110
Flammability - UL 94 - 1.6 mm
HB

Note: These are typical properties only.